HB Series (1kVA-10kVA) Double Conversion On-Line UPS
General Features
Double conversion high frequency on line technology
Reliable parallel N+1 technology
Complete protection functions
RS232/SNMP optional
Technical Specifications
Technology | Double Conversion High Frequency On-line Technology | |||
Input Voltage | 120-275V | |||
Input Frequency | 50/60Hz ㊣ 5% | |||
Output Voltage | 220/230V ㊣ 1% | |||
Output Frquency |
50/60Hz ㊣ 0.5Hz | |||
Output Waveform |
Pure Sine Wave | |||
Display |
LCD | |||
Transfer Time |
0ms |
|||
Automatic Bypass | Optional | |||
Manual Bypass | Optional | |||
Overload Ability | 1kVA-3kVA : 105-125% for 10s; above 125% for 0.2s | |||
6kVA-10kVA: 105-125% for 1min, 125-135% for 30s, above 135% for 0.1s | ||||
Crest Factor |
3:1 |
|||
THD (at 100% Load) |
<3% for linear load, <5% for non-linear load |
|||
RS232 Port |
Yes |
|||
RJ45/RJ11 Port |
Yes |
|||
Intelligent Slot | Yes | |||
SNMP Card | Optional | |||
Storage Temperature |
-15∼C ~ 45∼C |
|||
Operating Temperature |
-5∼C ~ 40∼C |
|||
Operating Humidity |
10%-90%, non-condensing |
Model No
Rated Power
Battery Voltage
No. of Battery
Backup Time (Full/Half Load)
Product Weight (kgs)
Product Size (DxWxH mm)
HBS-1K
1kVA / 0.8kW
36VDC
-
-
7.0
405 x 145 x 220
HB-1K92
24VDC
2 x 12V/9AH
4'/10'
12.0
HB-1K73
36VDC
3 x 12V/7AH
5'/13'
12.5
HBS-2K
2kVA / 1.6kW
72VDC
-
-
13.5
465 x 196 x 345
HB-2K94
48VDC
4 x 12V/9AH
4'/10'
30.0
HB-2K96
72VDC
6 x 12V/9AH
5'/13'
34.0
HBS-3K
3kVA / 2.4kW
96VDC
-
-
14.0
465 x 196 x 345
HB-3K96
72VDC
6 x 12V/9AH
4'/10'
34.5
HB-3K98
96VDC
8 x 12V/9AH
5'/13'
39.0
HBS-6K
6kVA / 4.8kW
192VDC
-
-
18.5
515 x 240 x 460
HB-6K916
192VDC
16 x 12V/9AH
4'/12'
15.6
515 x 250 x 616
HBS-10K
10kVA / 8kW
192VDC
-
-
20.0
515 x 240 x 460
HB-10K916
192VDC
16 x 12V/9AH
3'/10'
61.0
515 x 250 x 616